Cable and electrical
1 products
CableВВГ · 2×1,5 мм², 0,66 кВ · ГОСТ 16442-80 · +24 variantsSizes: 1×4, 2×1,5, 2×2,5, 3×1,5, 3×2,5, 3×4, 3×6, 3×10, 3×16, 3×25 · +8 morePrice on request
What the section includes
This section brings together cables for power transmission and distribution and products that protect and guide cable routes in buildings and industrial facilities. In the trade a power cable is often referred to by its type designation, VVG, a cable duct is called a cable trunking, and a flexible conduit is called a metal hose.
Product types
- Power cables – copper conductors with PVC insulation, for 0.66 and 1 kV networks in residential, public and industrial buildings.
- Cable trays – metal structures for open cable installation; together with cable brackets and posts they form the cable route.
- Cable ducts – trunking for neat routing of wiring along walls and ceilings.
- Flexible conduits – flexible metal hoses that protect cable from mechanical damage.
- Precision cable – special design; type and parameters are selected according to the project.
Power cable types and standards
In the designation, the first "V" stands for PVC conductor insulation, the second for a PVC sheath, and "G" for no armor; the figures give the number of conductors and their cross-section: VVG 3×2.5 means three conductors of 2.5 mm² each.
- VVG – unarmored, available as VVGp (flat) and VVGz (with filling between conductors); GOST 16442-80.
- VVGng – flame-retardant when laid in bundles; VVGng-LS – low smoke and gas emission when burning; VVGng-FRLS – fire-resistant; GOST 31996-2012.
- Armored (VBbShv; control cable – KVBbShv) – with steel tapes under the outer sheath, protected against rodents and mechanical loads.
Size range
- VVG: from 2×1.5 to 3×240 mm², rated voltage 0.66 and 1 kV.
- VVGng: from 2×1.5 to 3×120 mm², 0.66 and 1 kV.
- Number of conductors from 1 to 4, conductor cross-section from 1.5 to 240 mm².
Applications
VVG cable is installed in dry and damp rooms and outdoors; it is not laid in the ground without armor – armored types are required there, and they are also suitable for trenches and shafts. The ng-LS versions are chosen for public buildings, cable structures and bundled installation, where fire safety is important.
Cable products and cable routing components: VVG, VVGng, VVGng-LS and armored power cables with copper conductors rated 0.66 and 1 kV, cross-section from 1.5 to 240 mm², precision cable, cable trays, cable ducts and flexible conduits. Standards GOST 31996-2012 and GOST 16442-80. Supplied to order directly from the mills.